Series 603A Differential Pressure Transmitter
Specifications - Installation and Operating Instructions
Bulletin E-63A
DWYER INSTRUMENTS, INC.
Phone: 219/879-8000 www.dwyer-inst.com
P.O. BOX 373 • MICHIGAN CITY, IN 46361, U.S.A. Fax: 219/872-9057 e-mail: [email protected]
The Series 603A Differential Pressure Transmitter converts air or
compatible gas pressure into a standard 4-20 mA output signal for
pressure ranges from 0-.20 in. w.c. up to 30.0 psid (50 Pa up to 206.8
kPa). Each of these models overlap in range so that any range within
these pressure limits can be achieved by adjustment of the span and
zero controls located on the front of the transmitter. Positive, negative
or differential pressures can be measured within an accuracy (see chart)
of full span output.
STANDARD ACCESSORIES
Mounting ring, Snap ring
(4) 6-32 X 1-1/4˝ round head machine screws (panel mounting).
(3) 6-32 X 5/16˝ round head machine screws (surface mounting).
(2) Adapters, 3/16˝ I.D. tubing to 1/8˝ NPT.
(2) 1/8˝ NPT plugs.
Adjustment key for span and zero.
SPECIFICATIONS
Service: Air and non-combustible, compatible gases.
Wetted Materials: Consult factory.
Accuracy: (See Chart) (Includes linearity, hysteresis and repeatability).
Stability: ±1% F.S./yr.
Temperature Limits: 0 to 140°F (-17.8 to 60°C).
Compensated Temperature Limits: 20 to 120°F (-6.67 to 48.9°C).
Pressure Limits: See chart below.
Thermal Effect: ±0.025% F.S./°F (0.045% F.S./°C).
Power Requirements: 10-35 VDC (2-wire).
Output Signal: 4-20 mA.
Zero and Span Adjustments: External potentiometers.
Loop Resistance: DC; 0-1250 ohms.
Current Consumption: DC; 38 mA max.
Electrical Connections: 4 screw terminal block.
Process Connections: 1/8˝ female NPT.
Mounting Orientation: Diaphragm in vertical position.
Consult factory for other position orientations.
Weight: 1 lb, 10 oz (737 g).
Agency Approvals: CE.
* Optional 3, 4 wire configurations available, contact factory.
36°
21/32
[16.66]
1/8 FEMALE
NPT HIGH
PRESSURE
CONNECTION
1-3/4
[44.45]
1/2 [12.70]
11/16
[17.46]
(3) Ø3/16 [4.77] HOLES
EQUALLY SPACED ON A
4-1/8 [104.78] B.C.
SURFACE MOUNTING
1/8 FEMALE NPT
LOW PRESSURE
CONNECTION
1-25/64
[35.32]
1-1/2
[38.10]
9/16
[14.29]
2-1/16
[52.39]
2
[50.80]
1-1/4
[31.75]
1/8 FEMALE NPT
HIGH PRESSURE
CONNECTION
1/8 FEMALE NPT
LOW PRESSURE
CONNECTION
(4) 6-32 HOLES
EQUALLY SPACED ON
A 5-18 [130.18] B.C.
PANEL MOUNTING
Ø5
[127.00]
Ø4-47/64
[120.25]
5/8
[15.88]
5/8 [15.88]
PANEL MAX
3/16
[4.76]
2-1/2
[63.50]
Ø4 [101.60]
FACE
5-1/2 [139.70] O.D.
MOUNTING RING
ZERO
SPAN
DWYER INSTRUMENTS, INC.
Ranges in Inches W.C. (mm)
Model
603A-1
603A-2
603A-3
603A-4
603A-5
603A-6
603A-11
603A-12
603A-13
603A-14
603A-7
603A-8
As Stocked
0-.25 (6.34 mm)
0-0.50 (12.7 mm)
0-2.0 (50.8 mm)
0-5.0 (127 mm)
0-25 (634 mm)
0-100 (2540 mm)
.25-0-.25 (12.7 mm)
1-0-1 (50.8 mm)
5-0-5 (254 mm)
10-0-10 (508 mm)
0-20 (0-137.9)
3-15 (20.7-103.4)
Minimum
0-0.20 (5.08 mm)
0-0.50 (12.7 mm)
0-1.5 (38.1 mm)
0-4.0 (101.6 mm)
0-10 (254 mm)
0-50 (1264 mm)
0-10 (68.95)
Maximum
0-0.50 (12.7 mm)
0-1.50 (38.1 mm)
0-5.0 (127 mm)
0-15 (381 mm)
0-60 (1522 mm)
0-250 (6445 mm)
0-30 (206.8)
Ranges in PSID (kPa)
Electrical Accuracy
± %
2
2
0.5
0.5
0.5
0.5
2
0.5
0.5
0.5
0.5
0.5
Maximum Pressure
25 psi (1.7 bar)
25 psi (1.7 bar)
2 psi (13.8 kPa)
5 psi (34.5 kPa)
11 psi (75.8 kPa)
20 psi (1.4 bar)
25 psi (1.7 bar)
2 psi (13.8 kPa)
5 psi (34.5 kPa)
11 psi (75.8 kPa)
58 psi (4 bar)
30 psi (2.07 bar)
E-63A:E-63A 4/26/10 2:30 PM Page 1
Vedere la pagina 0
1 2 3 4

Sommario

Pagina 1 - DWYER INSTRUMENTS, INC

Series 603A Differential Pressure TransmitterSpecifications - Installation and Operating InstructionsBulletin E-63ADWYER INSTRUMENTS, INC. Phone: 219/

Pagina 2

INSTALLATIONLOCATION: Select a clean, dry location free from shock and vibrationwhere temperature limits will not be exceeded. Distance from thetransm

Pagina 3

ELECTRICAL CONNECTIONSCAUTION: Do not exceed specified supply voltage ratings. Permanent damage not covered by warranty will result. This unit isnot d

Pagina 4

MAINTENANCEAfter final installation of the Series 603A Differential PressureTransmitter, no routine maintenance is necessary. A periodic check ofcalib